원전 설계기준 사고시 냉각재계통 부분정체로 인한 비대칭 열유동 혼합해석에 관한 연구

Asymmetric Thermal-Mixing Analysis due to Partial Loop Stagnation during Design Basis Accident of NPP

  • 발행 : 2003.03.31

초록

When a cold HPSI (High Pressure Safety Injection) fluid associated with a design basis accident, such as LOCA (Loss of Coolant Accident), enters the cold legs of a stagnated primary coolant loop, thermal stratification phenomena may arise due to incomplete mixing. If the stratified flow enters a reactor pressure vessel downcomer, severe thermal stresses are created in a radiation embrittled vessel wall by local overcooling. Previous thermal-mixing analyses have assumed that the thermal stratification phenomena generated in stagnated loop of a partially stagnated collant loop are neutralized in the vessel downcomer by strong flow from unstagnated loop. On the basis of these reasons, this paper presents the thermal-mixing analysis results in order to identify the fact that the cold plume generated in the vessel downcomer due to the thermal stratification phenomena of the stagnated loop is affected by the strong flow of the unstagnated loop.

키워드