Abstract
The total PCBs level in the transformer insulation oil samples using GC/ECD and HRGC/HRMS were ranged from 0.087 to $223.6{\mu}g/g$ and ranged from N.D. to $154.04{\mu}g/g$, respectively. The calculated TEQ values were ranged from 0.00067 to 6.8 ng WHO-TEQ/g. Among the samples, 6 samples showed higher than 2 ppm concentration (specific waste criterion of Korea). A variety in the concentration of total PCBs were observed between ECD and HRMS analysis. This is maybe due to quantification mehtod. The Aroclor 1248 wasn't present in the samples. The distribution pattern of Co-PCB congeners showed that the ratio of monoortho substituted congeners were higher than non-ortho substituted congeners. Among that, PCB-167 congener was predominant. In addition, the distribution of Co-PCBs congeners was different with that of flue gas and ambient air samples as well as commercial PCB formulations (Aroclor, Kanechlor).
절연유 중 PCBs 총 농도를 GC/ECD와 HRGC/HRMS를 이용하여 정량한 결과 각각 N.D. ${\sim}154.04{\mu}g/g$과 $0.087{\sim}223.6{\mu}g/g$(TEQ 농도는 0.00067~6.8 ng WHO-TEQ/g)으로 검출되었으며, 6개의 시료에서 2 ppm을 초과하였다. 고농도 시료일수록 정량방법의 차이로 인해 ECD와 HRMS의 분석결과가 차이를 나타내었다. 절연유 중 PCBs의 피크패턴 및 군집분석을 사용하여 시료에 함유된 PCBs 제품형태를 추정할 수 있었으며, Aroclor 1248 제품은 함유되어 있지 않았다. Co-PCBs 이성체 분포에 있어서 non-ortho 치환 이성체에 비해 mono-ortho 치환 이성체가 높은 비율을 나타내었으며, PCB-167 이성체가 가장 높은 비율을 차지하였다. 또한 절연유 중 Co-PCBs의 이성체패턴은 소각로 배출가스, 환경 대기시료 뿐만 아니라 PCBs 제품(Aroclor, Kanechlor)과도 다른 이성체 패턴을 나타내었다.