DOI QR코드

DOI QR Code

Rack-Level DC Power Solution for Volume Servers

  • Kwon, Won-Ok (Software Research Laboratory, ETRI) ;
  • Seo, Hae-Moon (Department of Electrical Engineering, Kyungpook National University, Realistic Media Platform Research Center, KETI) ;
  • Choi, Pyung (Department of Electrical Engineering, Kyungpook National University)
  • 투고 : 2010.03.09
  • 심사 : 2010.09.06
  • 발행 : 2010.12.31

초록

Rack-level DC power supply is the optimal technology for providing DC power to a volume server without any power infrastructure changes in an existing AC data center. In this paper, we propose a smartly controllable and monitorable DC rack power system. The proposed system improves power efficiency by changing the power distribution architecture of a conventional method in the rack. We developed an optimal power control method in multipower modules to provide high efficiency at low loads. In addition, the proposed system provides real-time web monitoring of the rack power and environment around a rack. In our experiments, the proposed system improved the power efficiency by over 10% compared to an AC power system providing N+1 redundant power and power monitoring.

키워드

참고문헌

  1. S.L. Josselyn, "Worldwide and Regional Server 2007-2011 Forecast," IDC Market Analysis, Sept. 2007.
  2. U.S. EPA, "Report to Congress on Server and Data Center Energy Efficiency," U.S. Environmental Protection Agency, Tech. Rep., Aug. 2007.
  3. Green Grid Metrics: Describing Datacenter Power Efficiency, Green Grid Technical Committee White Paper, Feb. 2007.
  4. U. Hoelzle and B. Weihl, High-Efficiency Power Supplies for Home Computers and Servers, Google Inc. White Paper, Sept. 2006.
  5. W. Tschudi, M. Ton, and B. Fortenbery, "DC Power for Improved Data Center Efficiency," Report of High-Performance High-Tech Buildings Project, Lawrence Berkeley National Laboratory, Jan. 2007.
  6. A. Pratt, P. Kumar, and T.V. Aldridge, "Evaluation of 400 V DC Distribution in Telco and Data Centers to Improve Energy Efficiency," 29th Int. Telecommun. Energy Conf., 2007, pp. 32-39.
  7. B. Worrall, Building Energy-Efficient Datacenters, Sun Microsystems CIO, SUN Newsletter, Mar. 2007. Available at: http://www.sun.com/emrkt/innercircle/newsletter/0307sponsor.html.
  8. D. Meisner, B.T. Gold, and T.F. Wenisch, "PowerNap: Eliminating Server Idle Power," 14th Int. Conf. Architectural Support Programming Languages Operating Syst, Mar. 2009.
  9. K. Leigh and P. Ranganathan, "Blades as a General-Purpose Infrastructure for Future System Architectures: Challenges and Solutions," HP Labs, Tech. Rep. HPL-2006-182, Jan. 2007.
  10. N. Machin and T. Vescovi, "Important System Design Concepts for a Modular DC Rack Power System Featuring a Single Phase 100A, 48V Switch Mode Rectifier," 15th Int. Telecommun. Energy Conf., vol. 1, Sept. 1993. pp. 168-172.
  11. R. New and B.A. Wittey, "A Rack Mounted Complete DC Power System," Int. Telecommun. Energy Conf., Oct. 1982, pp. 270-276.
  12. DC Power Technology for High Efficiency and Reliability for Any Data Center, SGI AC-to-DC Power Rectification Solutions.
  13. B. Aebischer, "Energy Efficiency of Computer Power Supplies," Centre for Energy Policy and Economics, Swiss Federal Institute of Technology, 2007.
  14. C. Calwell, A. Mansoor, and R. Keefe, "Active Mode Power Supply Efficiency: Key Issues, Measured Data and the Design Competition Opportunity," IEEE APEC, vol. 1, 2004, pp. 323-328.
  15. P. Singh et al., "A Power, Packaging, and Cooling Overview of the IBM eServer z900," J. IBM Res. Dev., vol. 46, no. 6, Nov. 2002, pp. 711-738. https://doi.org/10.1147/rd.466.0711
  16. ATX12V Power Supply Design Guide Version 2.2, Intel Corp., Mar. 2005, p. 25.
  17. N. Rasmussen, "Electrical Efficiency Modeling for Data Centers," American Power Conversion, Tech. Rep. #113, 2007.
  18. Specification of Switching Power Supply, GIN-3800V, ZIPPY Technology Corp., Nov. 2007.
  19. J. Wiles, National Electrical Code, 2005 Ed., Quincy MA, National Fire Protection Association, 2005, p. 106.

피인용 문헌

  1. The Design of Marine 24 V DC Uninterruptible Power Supply vol.536, pp.None, 2014, https://doi.org/10.4028/www.scientific.net/amm.536-537.1537