DOI QR코드

DOI QR Code

패키지형 히트펌프 시스템이 적용된 실의 난방 시 드래프트에 의한 재실자 쾌적 특성

Characteristics of Occupants′ Comfort related to Draft during the Heating Operation in the Space with Packaged Terminal Heat Pump System

  • 투고 : 2015.04.30
  • 심사 : 2016.04.11
  • 발행 : 2016.04.30

초록

Packaged terminal heat pump systems, which are mainly used in small- and medium-sized buildings, are known to be cost-effective and thermally comfortable heating and cooling equipment. However, in practice, the issues of inefficient energy use as well as thermal discomfort have been discussed. Simplified design and application processes of packaged terminal heat pump systems can cause occupant thermal discomfort. In this study, the actual characteristics of occupant thermal comfort related to draft were analyzed during the operation of packaged terminal heat pump systems. Indoor thermal environment was evaluated by an Effective Draft Temperature(EDT) equation. The result shows that thermal discomfort occurred since 4-way type heat pump system is applied without careful consideration of the air temperature, velocity and indoor air distribution.

키워드

과제정보

연구 과제 주관 기관 : 한국연구재단

참고문헌

  1. ASHRAE. (2009). ASHRAE Handbook: Fundamentals, American Society of Heating, Refrigerating and Air-Conditioning Engineers, chapter 20
  2. Kang, K., Kang, K., Park, J., & Song, D., (2012). A Field Measurement for Indoor Thermal Environment and Thermal Comfort of Occupant in Office building controlled by Multi-System Air-conditioner, Korean Institute of Architectural Sustainable Environment and building Systems Spring Academic Conference, 89-94.
  3. Lee, J. (2005). Theoretical Study on the diffuser and indoor air distribution. Journal of Korean Association of Air Conditioning Refrigerating and Sanitary Engineers, 22(6), 34-44.
  4. Moon, E., Li, L., Jeong, C., Yeo, M., & Kim, K. (2014). Analysis on Thermal Comfort Related to Draft in Small and Medium-sized Building with Heat Pump HVAC System. Journal of the Architectural Institute of Korea Academic Conference, 34(1), 189-190.
  5. Shin, B., Kum, J., Ahn, C., Kim, D., Chung, Y., Choi, H., & Onishi, J. (2002). A Study on the Thermal Comfort by the Diffusion Direction with Ceiling Type Air Conditioner in Winter. Korean Journal of Air-Conditioning and Refrigeration Engineering Summer Academic Conference, 1199-1204.