국내 여름철 기후조건에서 DOAS와 TABS 통합시스템 냉방운전시 실내온열환경 및 운전특성 평가

Evaluation on the Indoor Thermal Environment and Cooling Operation Characteristics of Thermally Activated Building System integrated with Dedicated Outdoor Air System during Cooling Operation in Hot and Humid Climate of Seoul

  • 이윤선 (이화여자대학교 대학원) ;
  • 이겨레 (이화여자대학교 대학원) ;
  • 정웅준 (바스대 건축 및 토목공학과) ;
  • 임재한 (이화여자대학교 건축도시시스템공학과)
  • 투고 : 2018.07.31
  • 심사 : 2018.11.12
  • 발행 : 2018.11.30

초록

To reduce the energy consumption of HVAC system in buildings, thermally activated building system(TABS) has been applied to low energy building because of energy efficient performance and reduction of peak load. DOAS coupled with a parallel sensible cooling could be promising because TABS handles sensible heat load only. The purpose of this study was to evaluate the indoor thermal environment and cooling operation characteristic of TABS with dedicated outdoor air system(DOAS) in Korea climate. Indoor thermal environment and operation characteristic of TABS integrated with DOAS are investigated at different TABS operation schedules and climate conditions by simulation tests. The result shows that the DOAS is more suitable for hot and humid climates. And also it show that the potential of intermittent operation of TABS.

키워드

과제정보

연구 과제 주관 기관 : 한국연구재단

참고문헌

  1. ASHRAE Standard 62.1 (2007). Ventilation for Acceptable Indoor Air Quality.
  2. Chung, J.H., & Kim, S.B. (2013) A study on optical system configuration of the active chilled beam and dedicated outdoor air conditioning, Journal of the Society Of Air-Conditioning And Refrigerating Engineers of Korea, 733-737.
  3. Chung, W.J (2018). Improved thermally activated building system design method considering integration of air systems, Hindawi Advances in Civil Engineering, 2018.
  4. Dominguez, L.Marcos. (2017). Effects of acoustic ceiling units on the cooling performance of thermally activated building systems. Proceeding of the 2017 ASHRAE Winter Conference.
  5. Ha, D.W., & Huh, J.H. (2008) A study on the improvement of indoor air quality and energy performance through dedicated outdoor air system, Journal of The Korean Society of Living Environmental System, 15(1), 1-8.
  6. Inklab, N (2015). Performance Assessment of Dedicated Outdoorair Systems for Office Building in Thailand, Energy Procedia, 79, 677-684. https://doi.org/10.1016/j.egypro.2015.11.555
  7. ISO 11855-4 (2012). Building environment design - Design, dimensioning, installation and control of embedded radiant heating and cooling systems - Part 4 : Dimensioning and calculation of the dynamic heating and cooling capacity of Thermo Active Building Systems (TABS).
  8. Kim, M.H., Kim, J.H., Kwon, O.H., & Jeong, J.W (2009). Required supply air conditions and en-ergy saving potentials of dedicated outdoor air system with parallel cooling and heating in a high-rise apartment b-uilding, Journal of the Architectural Institute of Korea, P-lanning and Design Section, 25(6), 280-286.
  9. Jin, H.G. (2013). Evaluation of thermal comfort and energy performance for the radiant floor cooling system with dedicated outdoor air system in apartment building, Journal of the Architectural Institute of Korea, Planning and Design Section, 29(11), 273-281.
  10. Kim, H.J (2016). Energy benefit of a dedicated outdoor air system over a desiccant-enhanced evaporative air conditioner, Applied Thermal Engineering, 108, 804-815. https://doi.org/10.1016/j.applthermaleng.2016.07.185
  11. Kwon, O.H. (2010). Energy saving impact of Parallel cooling systems in a DOAS for school buildings, Journal of the Architectural Institute of Korea, 30(1), 443-444.
  12. Lim, H.S (2018). Energy saving potential of thermoelectric radiant cooling panels with a dedicated outdoor air system, Energy & Buildings, 169, 353-365. https://doi.org/10.1016/j.enbuild.2018.03.062
  13. National Renewable Energy Laboratory (2011). Department of Energy Commercial Reference Building Models of the National Building Stock; Technical Report; National Renewable Energy Laboratory: Golden, CO, USA.
  14. Park, S.H., Kim, I.M., Koo, S.Y., Yeo, M.S., & Kim, K.W. (2010) The effect on the heat output by combination of design factors of Thermally Activated Building system, Journal of the Korean Institute of Architectural Sustainable Environment and Building Systems, 4(3), 180-186.
  15. Xiao, Fu (2010). Control performance of a dedicated outdoor air system adopting liquid desiccant dehumidification, Applied Energy, 88, 143-149.
  16. Yasin, K (2015). Performance evaluation of radiant cooling system integrated with air system under different operational strategies, Energy and Buildings, 97, 118-128. https://doi.org/10.1016/j.enbuild.2015.03.030