DOI QR코드

DOI QR Code

일반공조 시스템 대비 축열조와 연동된 수직밀폐형 지열히트펌프의 냉난방 에너지 성능 및 경제성 분석

Cooling and Heating Energy Performance and Cost Analysis of Vertical Closed-loop Geothermal Heat Pump Coupled with Heat Storage Tank Compared to Conventional HVAC System

  • 김민지 (한밭대학교 대학원 건축공학과) ;
  • 도성록 (한밭대학교 설비공학과) ;
  • 최종민 (한밭대학교 기계공학과) ;
  • 이광호 (한밭대학교 건축공학과)
  • 투고 : 2018.09.07
  • 심사 : 2018.11.08
  • 발행 : 2018.11.30

초록

Among various types of geothermal heat pump systems, Vertical Closed-Loop Geothermal Heat Pump (VGSHP) has received increasing attention due to a variety of advantages such as the potential to be installed in a relatively small space and improved energy efficiency. In this research, the performance of VGSHP system coupled with heat storage tank was evaluated, by analyzing operational behavior of heat storage tank, the variations of heat pump energy performance due to the connection with heat storage tank, part load ratios characteristics of heat pump and the corresponding energy cost, compared to chiller and boiler based conventional system. The results of this study showed that the VGSHP system coupled with heat storage tank showed an energy saving effect of about 18% for cooling and about 73% for heating, and annual heating/cooling energy cost reduction of 43,000,000 KRW ($ 39,000), compared to the conventional air conditioning system. In addition, after considering both energy cost and initial investment cost including equipment, installation and auxiliary device expenses, payback period of approximately 11.8 years was required.

키워드

과제정보

연구 과제 주관 기관 : 한국에너지기술평가원(KETEP)

참고문헌

  1. Lee, K., Hong, J., & Kong, H. (2016). A study of comparative economic evaluation for the system of ground source heat pump and district heat and cooling : focusing on the analysis of operation case, Journal of the Society of Air-conditioning and Refrigerating Engineers of Korea , 28(3), 103-109. https://doi.org/10.6110/KJACR.2016.28.3.103
  2. Nam, Y., & Oh, J. (2014). Study on the characteristic of heat exchange for vertical geothermal system using the numerical simulation, Journal of the Korean Solar Energy Society, 34(2), 66-72. https://doi.org/10.7836/kses.2014.34.2.066
  3. Lim, H. (2010). Ground source heat pump, Journal of the Society of Air-conditioning and Refrigerating Engineers of Korea , 39(2), 22-32.
  4. Woo, S., Hwang, K., Kim, J., & Shin, S. (2007). A performance prediction of a vertical-type geothermal heat exchanger by CFD analysis, Journal of the Korean Solar Energy Society, 27(3), 117-125.
  5. Sun, J., Kim, B., & Koh, Y. (2013). The characteristics of thermal diffusion with the vertical-closed loop type ge othermal heat exchanger, Journal of the Korean Solar Energy Society, 33(1), 57-65. https://doi.org/10.7836/kses.2013.33.1.057
  6. Hoseyn S., Emad, H., & Majid, A. (2009). Multi-objective optimization of a vertical ground source heat pump using evolutionary algorithm, Energy Conversion and Management, 50, 2035-2046. https://doi.org/10.1016/j.enconman.2009.04.006
  7. Kim, M., Seo, B., Lee, J., Choi, J., & Lee, K. (2018). Operational behavior characteristics and energy saving potential of vertical closed loop ground source heat pump system combined with storage tank in and office building, Energy and Buildings, Vol. 178, pp. 239 - 252.
  8. The U. S. Department of Energy (2016). EnergyPlus Input Output Reference, The Encyclopedic Reference to EnergyPlus Input and Output.
  9. Hyun, I. (2016). Development of performance curve coefficients and its verification method for variable refrigerant flow heat pump system in EnergyPlus, Master's Thesis, Hanbat National University.
  10. Korea Electric Power Corporation. (2016). Available online : http://cyber.kepco.co.kr/ckepco.
  11. Korea Energy Agency. (2018). Available online : http://www.kogas.or.kr/portal/contents.do?key=2024.
  12. Nam, Y., & Chae, B. (2014). The performance test and the feasibility study for a dual- source heat pump system using the air and ground heat source, Journal of the Society of Air-conditioning and Refrigerating Engineers of Korea, 26(5), 212-217. https://doi.org/10.6110/KJACR.2014.26.5.212