초록

The management of airtightness of houses has been widely studied, while the airtightness of school buildings is still required to investigate. Therefore, the improvement action for the infiltration of fine dust is introduced in this paper. To measure the infiltration of fine dust, airtightness and indoor/outdoor fine dust concentration are obtained and then the infiltration path of outdoor fine dust concentration is identified at six schools in Busan, Korea. Then a series of experiments is conducted and provided following results. The average of amount of airtightness for target classroom is 14.9 ACH50 which is much higher than KIAEBS standard (5.0 ACH50) and ASHRAE commercial building standard (1.4 ~ 2.1 ACH50). The infiltration of school classroom is measured as following order, corridor window (61.3%), exterior window (27.9%), and mechanical ventilation (10.8%), meaning that a large amount of outdoor air is introduced from corridor wood windows and doors. The I/O ratio of PM 10 and PM 2.5 is increased when airtightness is getting worse. Consequently, it is found that the improvement of airtightness needs to be preceded to reduce indoor fine dust.

키워드

과제정보

이 연구는 한국연구재단 연구비 지원에 의한 결과의 일부임. 과제번호:2019M3E7A1113088

참고문헌

  1. Kim, S. C. (2019). Investigation of the Concentration of PM2.1 & PM10 and Alveolar Deposition Ratio, J Environ Health Sci, 45(2), 126-133
  2. Lee, Y. G., & Shin, C. W. (2013). The Air Leakage Characteristics and Airtightness Performance of a Newly Built Apartment, Korean Journal of Air-Conditioning and Refrigeration Engineering, 25(11), 606-611. https://doi.org/10.6110/KJACR.2013.25.11.606
  3. Jeong, S. M., Park, H. C., Kim, S. H., & Yee, J. J. (2018). A Study on the Inflow of Fine Dust Concentration Variation due to External Wind Speed into School Buildings, Korean Institute of Architectural Sustainable Environment and Building Systems, 87-88.
  4. Lee, J. Y., Lee, D. H., Kim, T. J., & Yee, J. J. (2019). A Study on the Measurement of Airtightness and the Variation Characteristics of CO2 Concentration in Schools, BUSAN.ULSAN.CYEONGNAM CHAPTER OF ARCHITECTURAL INSTITUTE OF KOREA, 131-132
  5. Shin, H. K., & Jo, J. H. (2011). Comparison of Test Conditions of the Fan Pressurization Method in measuring the Building Airtightness, Journal of the Architectural Institute of Korea Planning & Design, 279-286
  6. ASHRAE Standard 119, "Air Leakage Performance for Detached Single-Family esidential Buildings", American Society of Heating, Refrigerating and Air conditioning Engineers, 1988.
  7. Germany Airtightness performance standard, "DIN 4108-7 and EnEV", 2008.
  8. Japan Airtightness performance standard, "Energy conservation standard"
  9. Korea Airtightness performance standard, "Building Airtightness Criteria"(2013). Korean Institute of Architectural Sustainable Environment and Building System(KIAEBS)
  10. Air Korea (Korea Environment Corporation), "Standard of Fine Dust"
  11. Cho, S W, & Park, J. S.(2019). The effect of outdoor particles on the indoor particles concentration in daycare center, Korean Institute of Architectural Sustainable Environment and Building System (KIAEBS) 73-74
  12. Kwon, O. H., Kim, J. H., Kim, M. H., Seok, Y. J., & Jeong, J. W. (2010). Case Study of Residential Building Air Tightness in Korea based on Blower Door Test Approach, Journal of the Architectural Institute of Korea Planning & Design, 303-310
  13. Undram M., Song, D. S., & Kim, J. W. (2019). A Review of the Test Methods for Air-tightness Performance of Building Components Using the Blower Door System, Korean Journal of Air-Conditioning and Refrigeration Engineering, 216-226
  14. Kang, D. H., & Choi, D. H. (2015). A Preliminary Study to Evaluate the Impact of Outdoor Bust on Indoor Air by Measuring Indoor/Outdoor Particle Concentration in a Residential Housing Unit, Journal of Korean Institute of Architectural Sustainable Environment and Building System(KIAEBS), 452-459
  15. Back, J. M., Yee, S. W., Lee, B. H., Kang, D. H., Yeo, M. S., & Kim, K. W.(2015). A Study on the Relationship between the Indoor and Outdoor Particulate Matter Concentration by Infiltration in the Winter, Journal of the Architectural Institute of Korea Planning & Design, 137-144
  16. KS L ISO 9972(1996) - Thermal insulation - Determination of building airtightness - Fan pressurization method
  17. ASTM E779(2018) - Standard Test Method for Determining Air Leakage Rate by Fan Pressurization