Abstract

This study aimed to elucidate causes of corrosion of heat transport pipes and air vents installed under a manhole of heat transport facilities and suggest effective anticorrosive measures by applying paints or adhesive tapes. It was found that air vent corrosion was attributed to corrosion under insulation caused by the inflow of water and the enrichment of chloride ions. The infiltrated water caused a hydrolysis of polyurethane foam (PUF) insulation by concentrating chloride ions at the interface between a pipe and the PUF. As insulator deteriorated, more chloride ions were eluted as confirmed by ion chromatograph (IC) analysis. As an effective method to prevent air vent corrosion, different types of paints and adhesive tapes with higher corrosion resistance on chloride ions were applied and environmental resistance tests were performed with those samples. Based on environmental test results of samples exposed to 10% HCl solution, it was revealed that a wax tape was the most adequate from a viewpoint of stability at operating condition, environmental resistance, surface treatment, and field applicability.

Keywords

Acknowledgement

본 연구는 한국지역난방공사의 지원을 받아 연구를 수행하였습니다.

References

  1. J. Kim, Y. S. Kim, H. Kim, J. Yoon, Effect of operating temperature conditions in 21-year-old insulated pipe for a district heating network, Case studies in thermal engineering, 27, 101265 (2021). Doi: https://doi.org/10.1016/j.csite.2021.101265
  2. L. Doyle, I. Weidlich, Effects of thermal and mechanical cyclic loads on polyurethane pre-insulated pipes, Fatigue & Fracture of Engineering Materials & Structures, 44, 156 (2021). Doi: https://doi.org/10.1111/ffe.13347
  3. H. Kim, H. Chae, J. Cho, W.C. Kim, J.C. Jeong, H. Kim, J.G. Kim, S.Y. Lee, Corrosion failure analysis of air vents installed at heat transport pipe in district heating system, Corrosion Science and Technology, 19, 189 (2020). Doi: https://doi.org/10.14773/cst.2020.19.4.189
  4. J. Cho, H. Chae, H. Kim, J.G. Kim, W.C. Kim, J.C. Jeong, S.Y. Lee, Failure analysis of air vent connected with heat supply pipeline under manhole, Corrosion Science and Technology, 19, 196 (2020). Doi: https://doi.org/10.14773/cst.2020.19.4.189
  5. Y.S. Kim, H. Chae, W.C. Kim, J.C. Jeong, H. Kim, J.G. Kim, S.Y. Lee, Failure analysis on localized corrosion of heat transport pipe in district heating system, Corrosion Science and Technology, 19, 122 (2020). Doi: https://doi.org/10.14773/cst.2020.19.3.122
  6. H.S. Kim, G.B. Kim, L.H. Kim, Development of a failure probability model based on operation data of thermal piping network in district heating system, Korean chemical engineering research, 55, 322 (2018). Doi: https://doi.org/10.9713/kcer.2017.55.3.322
  7. H. Song, E. Lee, D. Jung, I. Kim, Seasonal and regional concentrations of chemical composition in rainwater in daegu area, Journal of Korean Society of Environmental Engineers, 28, 522 (2006). Doi: https://doi.org/10.1016/S1352-2310(01)00198-4
  8. G. Jung, J. Lee, W. Kim, J. Kim, S. Yun, Wet Deposition of Heavy metals in Suwon Area, Korean Journal of Environmental Agriculture, 26, 116 (2007). Doi: https://doi.org/10.5338/KJEA.2007.26.2.116
  9. Y. Song, G. Jiang, Y. Chen, P. Zhao, Y. Tian, Effects of chloride ions on corrosion of ductile iron and carbon steel in soil environments, Scientific reports, 7, 6865 (2017). Doi: https://doi.org/10.1038/s41598-017-07245-1
  10. Q. Gao, Y. Pojtanabuntoeng, M. Esmaily, S. Thomas, M. Brameld, A. Amer, N. Birbilis, A review of corrosion under insulation: A critical issue in oil and gas industry, Metals, 12, 561 (2022). Doi: https://doi.org/10.3390/met12040561
  11. S. Hoerle, F. Mazaudier, Ph. Dillmann, G. Santarini, Advances in understanding atmospheric corrosion of iron. II. Mechanistic modelling of wet-dry cycles, Corrosion science, 46, 1431 (2004). Doi: https://doi.org/10.1016/j.corsci.2003.09.028
  12. E. D. Mackey, T. F. Seacord, Guidelines for using stainless steel in the water and desalination industries, Journal American Water Works Association, 5, 158 (2017). Doi: https://doi.org/10.5942/jawwa.2017.109.004
  13. S. Kim, J. Lee, J. Kim, W. Kim, Effect of the crevice former on the corrosion behavior of 316l stainless steel in chloride-containing synthetic tap water, Metals and materials international, 24, 516 (2018). Doi: https://doi.org/10.1007/s12540-018-0062-2